INSP-Final Inspection | 2/20/2008 | 2/21/2008 | 2/21/2008 | A | PASS |
Forrest France
|
|
|
Fire sprinkler inspection comleted. KR
|
INSP-Sprinkler Rough-in | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | PART |
Forrest France
|
|
|
UG fire supply line flush completed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/20/2007 | 11/20/2007 | A | PART |
Forrest France
|
|
|
UG supply line hydro test passed.
|
INSP-Sprinkler Rough-in | 8/22/2007 | 8/23/2007 | 8/23/2007 | A | PART |
Forrest France
|
|
|
UG fire supply line from the stub in at the foundation to the PIV only is okay for cover. Also inspected UG fire supply lines for the other three buildings not separately requested for inspection under respective FIR #'s as will be required for hydrostatic and flushing inspections.
|
INSP-Sprinkler Rough-in | 8/16/2007 | 8/17/2007 | 8/17/2007 | A | PART |
Forrest France
|
|
|
DSW head installation at the second floor unit balconies appears acceptable, need approved plans on site for verification at next scheduled inspection.
|
INSP-Sprinkler Rough-in | 8/15/2007 | 8/16/2007 | 8/16/2007 | P | CANC |
Forrest France
|
|
|
Overbooked, no time available for this inspection today.
|
INSP-Sprinkler Rough-in/Hydro | 6/12/2007 | 6/13/2007 | 6/13/2007 | A | PASS |
Troy Cobbley
|
|
|
The above ground hydro test of both risers passed.
|
INSP-Sprinkler Rough-in/Hydro | 6/11/2007 | 6/12/2007 | 6/12/2007 | A | FAIL |
Forrest France
|
|
|
No hydrostatic test completed due to start pressures well below 200 psi., noted riser manifolds will need to be adjusted to provide access to the flow switches, recommend nailer plates be installed at 1.5" risers to the 2nd floor. C/N items from the previous inspection and tenting for the second floor are acceptable.
|
INSP-Sprinkler Rough-in/Hydro | 6/5/2007 | 6/7/2007 | 6/11/2007 | A | FAIL |
Forrest France
|
|
|
Missing proper hangers at the FDC piping, one utility room pendent is missing a hanger, need correct temp. SW head at a first floor bedroom, piping at two locations adjacent to the 1st floor carports are subject to freeze potential as installed, missing head at the riser, overspaced heads at the 2nd floor in three units, need to verifiy tenting prior to approval for cover.
|