INSP-Final Inspection | 2/21/2008 | 2/22/2008 | 2/22/2008 | P | PASS |
Forrest France
|
|
|
All corrections were made per last inspection. KR
|
INSP-Supply line flush | 2/20/2008 | 2/21/2008 | 2/21/2008 | A | FAIL |
Forrest France
|
|
|
See city approved plans with red lined notes. Back flow need cert,missing sprinkler head in ac, water heater closet on south west corner of building. Some heads covered with tape. see red lined notes for locations. KR
|
INSP-Sprinkler Rough-in | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | PART |
Forrest France
|
|
|
Underground flush passed as per KR
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/20/2007 | 11/20/2007 | A | PART |
Forrest France
|
|
|
UG fire supply line hydrostatic test passed.
|
INSP-Sprinkler Rough-in | 8/30/2007 | 8/31/2007 | 8/31/2007 | A | PART |
Forrest France
|
|
|
DSW heads at building #2 second and third floors are approved for cover, discussed schedule for bld #3.
|
INSP-Sprinkler Rough-in | 8/29/2007 | 8/30/2007 | 8/30/2007 | A | CANC |
Forrest France
|
|
|
Overbooked
|
INSP-Sprinkler Rough-in/Hydro | 7/9/2007 | 7/10/2007 | 7/10/2007 | A | FAIL |
Forrest France
|
|
|
Per requirements of IFC 2003 903.3.1.2.1 sprinkler protection shall be provided for exterior balconies and ground floor patios of dwelling units protected by a 13R system. The overhead hydrostatic testing for building 2 completed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 7/6/2007 | 7/9/2007 | 7/10/2007 | P | FAIL |
Forrest France
|
|
|
Some items noted at the previous inspection have been completed, various hangers are not correctly installed according to the listing, missing hangers at some locations.
|
INSP-Sprinkler Rough-in/Hydro | 7/3/2007 | 7/5/2007 | 7/5/2007 | P | FAIL |
Forrest France
|
|
|
OH rough-in is not approved for cover until system piping is correctly attatched to the structure as required, missing hangers and upward restraint at several locations, noted some heads have been added and piping relocated from approved plan set, OH hydro test not ready at this time due to pressure loss, tenting appears adequate.
|
INSP-Sprinkler Rough-in/Hydro | 6/29/2007 | 7/2/2007 | 7/2/2007 | P | CANC |
Forrest France
|
|
|
Please call 1/2 hr prior to inspection. Brian F. is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|