Permit Information
Permit NumberFIR07-00234
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1463 W GRAND ST
Project NameGRAND AVE HOMES BLDG #2
Customer Number 
ePlanReview 
Description
Revised Scope of Work
To install a fire life safety NFPA 13R system to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated, in a new 9,316-ft/2 three story, apartment building. An NFPA 13R fire sprinkler protection system is required. The system shall be equipped with separate systems and controls for each unit and an alarm initiating device connected to an alarm system and an outside annunciating devise. All fire sprinkler work and related, which includes dual service underground water supply, the system backflow prevention device (provided by others), shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-00075.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/21/20082/22/20082/22/2008PPASS
DetailsForrest France
All corrections were made per last inspection. KR
INSP-Supply line flush2/20/20082/21/20082/21/2008AFAIL
DetailsForrest France
See city approved plans with red lined notes.
Back flow need cert,missing sprinkler head in ac, water heater closet on south west corner of building. Some heads covered with tape. see red lined notes for locations. KR
INSP-Sprinkler Rough-in11/26/200711/27/200711/27/2007APART
DetailsForrest France
Underground flush passed as per KR
INSP-Sprinkler Rough-in/Hydro11/16/200711/20/200711/20/2007APART
DetailsForrest France
UG fire supply line hydrostatic test passed.
INSP-Sprinkler Rough-in8/30/20078/31/20078/31/2007APART
DetailsForrest France
DSW heads at building #2 second and third floors are approved for cover, discussed schedule for bld #3.
INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007ACANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in/Hydro7/9/20077/10/20077/10/2007AFAIL
DetailsForrest France
Per requirements of IFC 2003 903.3.1.2.1 sprinkler protection shall be provided for exterior balconies and ground floor patios of dwelling units protected by a 13R system. The overhead hydrostatic testing for building 2 completed satisfactory.
INSP-Sprinkler Rough-in/Hydro7/6/20077/9/20077/10/2007PFAIL
DetailsForrest France
Some items noted at the previous inspection have been completed, various hangers are not correctly installed according to the listing, missing hangers at some locations.
INSP-Sprinkler Rough-in/Hydro7/3/20077/5/20077/5/2007PFAIL
DetailsForrest France
OH rough-in is not approved for cover until system piping is correctly attatched to the structure as required, missing hangers and upward restraint at several locations, noted some heads have been added and piping relocated from approved plan set, OH hydro test not ready at this time due to pressure loss, tenting appears adequate.
INSP-Sprinkler Rough-in/Hydro6/29/20077/2/20077/2/2007PCANC
DetailsForrest France
Please call 1/2 hr prior to inspection. Brian F. is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus