Permit NumberFIR07-00240
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 950 W BANNOCK ST Unit: 400
Project Name10TH & BANNOCK
Customer Number 
ePlanReview 
Description
The Permitted Work Scope:
Add 27 SSP heads & relocate 13 others to accommodate a new wall and ceiling layout on the 4th floor of this high rise bldg. A new double interlock preaction system will be added to serve the Data Room #419. A new Croker pressure regulating valve will be installed up-line from the Pre-Action riser. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00047. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/9/20075/10/20075/10/2007APASS
DetailsForrest France
Final FS permit inspection passed, corrections complete.
INSP-Final Inspection5/4/20075/7/20075/7/2007APART
DetailsForrest France
Pending ceiling tile, lockout at the air comp. switch as discussed.
INSP-Sprinkler Rough-in/Hydro5/2/20075/3/20075/3/2007PPART
DetailsForrest France
Air testing for the preaction system passed inspection.
INSP-Sprinkler Rough-in/Hydro5/2/20075/2/20075/2/2007PPART
DetailsForrest France
Begin air test 2:35 pm @ 52psi. as marked on guage.
INSP-Sprinkler Rough-in5/1/20075/2/20075/2/2007APART
DetailsForrest France
OH installation is acceptable, hydrostatic test of the preaction system completed, noted changes at preaction riser including drain termination point, different PRV than what is submitted, riser trim has been modified to include a potter ps40 in lieu of the mfg. supplied pressure switch.