INSP-Final Inspection | 2/8/2008 | 2/11/2008 | 2/11/2008 | A | PASS |
Forrest France
|
|
|
Fire sprinkler system final testing passed, previous correction items are complete, plan resubmittals provided, three defficiencies noted at today's inspection repaired while on site, dry system trip test and DCVA forward flow testing passed. See project related permit FIR06-00727 for the balance of activities and inspections completed for this overhead work listed under the UG permit due to contractor mixing permit #'s for site inspeciton requests.
|
INSP-Final Inspection | 1/24/2008 | 1/28/2008 | 1/28/2008 | P | FAIL |
Forrest France
|
|
|
Need plan resubmittals per field inspection notes completed 6/27/07 for the dry system modifications, the paddle style waterflow switch at the dry system riser is not allowed, provide a QR head at the first floor SE storage room, need to provide a seal or lock at the ball valve to the pressure switch at the dry system trim, noted mixed response heads at three rooms on the second floor including 212 and 223, one head at room 236 is obstructed by a light fixture, noted items from the previous inspection at the 1st floor are complete, inspection concluded at this time due to time constraints.
|
INSP-Sprinkler Rough-in | 1/14/2008 | 1/18/2008 | 1/18/2008 | A | PART |
Forrest France
|
|
|
First floor corridor fire sprinklers are okay for cover with the exception of two pendents in need of relocation due to overspacing from adjacent vestibules to the meeting room, also noted one head blocked by a 4' soffit at the lobby, missing head at the laundry chute termination room, discussed head location at a mech. room, the elevator pit head is not yet installed, missing escutcheons at some locations.
|
INSP-Sprinkler Rough-in/Hydro | 8/9/2007 | 8/10/2007 | 8/10/2007 | A | PART |
Forrest France
|
|
|
Heads at the laundry chute are okay for cover, noted one hanger at the 2nd floor piping to the chute in need of attatchment.
|