Permit Information
Permit NumberFIR07-00248
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 8512 W ELISA ST
Project NameSPR-Underground BLNG "C"
Customer Number 
ePlanReview 
Description
Victory Business Park - Building "C" - To build a new 14,100 square foot, one story with mezzanine office and warehouse building and related site improvements. Debest Fire Protection to install approximately 92 LF of 6" C-900 under ground sprinlker supply piping for fire protection system. No overhead fire sprinkler work is permitted under this sprinkler permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/7/20085/7/20085/7/2008PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro6/27/20076/28/20076/29/2007PPASS
DetailsTroy Cobbley
UG Flush passed
INSP-Supply line flush6/26/20076/27/20076/27/2007AFAIL
DetailsTroy Cobbley
UG Flush Inspection was not ready. I performed a partial sprinkler rough-in and noted deficiencies such as upright heads blocked by duct work, missing protection under stair landings and upright heads not centered between the trusses.
INSP-Sprinkler Rough-in4/23/20074/24/20074/24/2007PPASS
DetailsTroy Cobbley
Underground supply piping is ok to cover
INSP-Sprinkler Rough-in/Hydro3/21/20073/22/20073/22/2007APASS
DetailsTroy Cobbley
The underground stub-out and 20"-0" of pipe from the stubout is ok to bury.