INSP-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 | A | PASS |
Forrest France
|
|
|
Required corrections verified for compliance, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 7/25/2007 | 7/25/2007 | 7/25/2007 | A | PART |
Forrest France
|
|
|
Preaction system passed 24 hr. air test.
|
INSP-Sprinkler Rough-in/Hydro | 7/23/2007 | 7/24/2007 | 7/24/2007 | A | PART |
Forrest France
|
|
|
Begin 24 hr. air testing of the preaction system at 10:20 @ 40 psig.
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2007 | 7/23/2007 | 7/23/2007 | A | PART |
Forrest France
|
|
|
OH hydrostatic test completed satisfactory, need to provide seismic clearance for the 6" main as indicated on approved plans, one upright head is installed too low.
|