INSP-Final Inspection | 12/7/2007 | 12/7/2007 | 12/7/2007 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | PASS |
Forrest France
|
|
|
Final pending NFPA 72 forms.
|
INSP-Final Inspection | 12/5/2007 | 12/5/2007 | 12/5/2007 | P | PART |
Forrest France
|
|
|
Corrections have been verified, okay for final when shell and core alarm permit is finaled.
|
INSP-Final Inspection | 12/3/2007 | 12/4/2007 | 12/4/2007 | A | FAIL |
Forrest France
|
|
|
The door closure at the trash chute is not properly adjusted.
|
INSP-Final Inspection | 11/27/2007 | 11/28/2007 | 11/28/2007 | A | DEFR |
Forrest France
|
|
|
See inspection comments per M. Timmerman.
|
INSP-Final Inspection | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | CANC |
Forrest France
|
|
|
Overbooked.
|
INSP-Alarm Testing | 11/26/2007 | 11/26/2007 | 11/26/2007 | P | DEFR |
Forrest France
|
|
|
Inspection request intended for the shell and core alarm work, items tested today include fire sprinkler monitoring of the fire pump, controller, power supplies, dry system, tampers, flows, etc. Outside bell does not function at pump flow switch, need 12 ah batteries at the FACP, tamper at the standpipe control valve is not correct.
|
FIR-Aging Inspection | 10/24/2007 | 10/24/2007 | 10/24/2007 | | DEFR |
Forrest France
|
|
|
work in progress
|