Permit Information
Permit NumberFIR07-00336
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 8512 W ELISA ST
Project NameVictory Business Park BLD C
Customer Number 
ePlanReview 
Description
Overhead system only under this review. Install a wet pipe system through out the new structure. The system is designed to protect Class IV commodities up to 16'-0" in a solid pile configuration. No rack storage has been reviewed or approved under this permit. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-02010. This permit is attached to Under Ground permit # FIR07-0024807/20/07 Revised Scope of Work:
In addition to the original scope of work, the contractor added 13 additional heads in the heated attic to meet code compliance. No rack storage has been reviewed or approved under this permit.
Original Scope of Work:
Overhead system only under this review. Install a wet pipe system through out the new structure. The system is designed to protect Class IV commodities up to 16’-0” in a solid pile configuration. No rack storage has been reviewed or approved under this permit. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-02010. This permit is attached to Under Ground permit # FIR07-00248.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/16/200711/19/200711/19/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection11/9/200711/13/200711/13/2007AFAIL
DetailsTroy Cobbley
Forward flush passed but the alarm portion failed
INSP-Final Inspection11/5/200711/7/200711/7/2007PCANC
DetailsTroy Cobbley
Todd and I agreed to reschedule for friday morning at 8:00
INSP-Sprinkler Rough-in/Hydro11/1/200711/2/200711/2/2007PCANC
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Sprinkler Rough-in/Hydro10/25/200710/26/200710/26/2007AFAIL
DetailsTroy Cobbley
OH hydro test failed
INSP-Sprinkler Rough-in/Hydro10/24/200710/25/200710/25/2007PFAIL
DetailsTroy Cobbley
Inspection was scheduled for afternoon but due to Micron I tried to do it this morning. I found the guage below 200 psi and the fdc and the riser/header not part of the test.
INSP-Sprinkler Rough-in/Hydro9/19/20079/20/20079/20/2007APART
DetailsTroy Cobbley
The first floor system passed but the upper level piping hydro test failed. Also the fire dept connection needs hydro tested.
INSP-Final Inspection9/18/20079/19/20079/19/2007ACANC
DetailsTroy Cobbley
Final Inspection
Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in8/21/20078/22/20078/22/2007APASS
DetailsTroy Cobbley
OH Cover Inspection passed. Some of the upright heads still have tape on them in the warehouse area and under the stairs. I will check these at the final.
INSP-Sprinkler Rough-in6/29/20077/2/20077/3/2007PPASS
DetailsTroy Cobbley
Overhead sprinkler piping is ok to cover. The trapezes need to be drilled to secure the main piping. This will be checked at the final.