Permit Information
Permit NumberFIR07-00338
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 4313- 4315 W ALBION
Project Name4313 & 4315
Customer Number 
ePlanReview 
Description
Scope of Work
Beginning from the supply side of the Back Flow Device, (Supplied By Others). Install a life safety modified NFPA 13D system in a new one story duplex. 2,426-ft/2. (Units 4313 & 4315 Combined). The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-03388.08/28/07 Revised Scope of Work
This plan review is a result of changes made in the field during construction that warranted a complete resubmittal including a revised set of calculations. A new riser location has been noted on the plans dated 08/09/07 noted as Revision #1.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/30/20081/31/20081/31/2008APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in9/6/20079/7/20079/7/2007APASS
DetailsTroy Cobbley
Some tenting modification was required but is now ok to cover
INSP-Sprinkler Rough-in/Hydro7/31/20078/1/20078/1/2007AFAIL
DetailsTroy Cobbley
The plans do not match the installation. For example the riser has been relocated 15' south and two additional rooms have been added to the building which will cause the remote area to be moved to the south. The backflow device installed is not what was submitted. Additional hangers are required. The riser has been installed as cpvc and does not meet the installation requirements of cpvc installation. The plans show the riser to be sch 40 galv. Plans need to be resubmitted. I only looked at the south most building before stopping the inspection