Permit Information
Permit NumberFIR07-00348
StatusFinaled
Name DELTA FIRE SYSTEMS
Site Address 1111 W JEFFERSON ST
Project NameBoise Cascade Building
Customer Number 
ePlanReview 
Description
Revised Scope of Work
Basement: Complete sprinkler coverage in the Computer Equipment Rm. 156 as agreed upon. The seismic bracing on the basement level will also be brought up to code under this permit. All fire sprinkler and standpipe work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This fire permit is attached to building permit: BLD06-01188 & FIR06-00540.08/30/07 Revised Scope of Work
Basement: Complete sprinkler coverage in the Computer Equipment Rm. 156 by modifying the existing head layout to accommodate a new clg.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/4/200710/4/200710/4/2007PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in/Hydro10/2/200710/3/200710/4/2007PPASS
DetailsForrest France
The remainder of seismic upgrade work has been completed, inspection passed.
INSP-Sprinkler Rough-in/Hydro9/28/200710/2/200710/2/2007APART
DetailsForrest France
See annotations on plan for areas approved related to the seismic upgrade, mechanical and boiler room areas not inspected at this time.
INSP-Sprinkler Rough-in/Hydro9/21/20079/24/20079/24/2007APART
DetailsForrest France
Seismic upgrade work for the basement level west half as noted on plans is acceptable, no access to the ceiling above the locker room at this time, noted one location not completed, verified main is connected for the new computer and storage room heads.
INSP-Sprinkler Rough-in/Hydro9/13/20079/14/20079/14/2007APART
DetailsForrest France
OH install as circled and initialed on the approved plan set for the office storage and computer room areas is approved for cover, need to verify connection to the existing main when complete, hydrostatic test for this area passed although not required per NFPA as the modification is less than 20 heads.