Permit NumberFIR07-00420
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 190 E BANNOCK ST
Project Name 
Customer Number 
ePlanReview 
Description
Scope of Work: Overhead Only
Install a single interlock pre-action system in the Phone room at the basement level of the bldg. The system will serve the room on two levels including a sub floor. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any other permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/7/200711/7/200711/7/2007PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in/Hydro11/6/200711/7/200711/7/2007PPART
DetailsForrest France
Hydrostatic testing of the preaction system piping completed per K. Roule.
INSP-Sprinkler Rough-in/Hydro11/6/200711/6/200711/6/2007PPART
DetailsForrest France
Pneumatic testing for the preaction system passed within allowable pressure loss of 1 1/2 psig.
INSP-Final Inspection11/1/200711/5/200711/5/2007PPART
DetailsForrest France
Begin 24hr. pneumatic testing of the preaction system at 41psi.@11:40am.
INSP-Sprinkler Rough-in/Hydro11/1/200711/5/200711/5/2007PPART
DetailsForrest France
Fire sprinkler rough-in completed acceptable.