Permit Information
Permit NumberFIR07-00472
StatusFinaled
Name PROTEX
Site Address 1112 W MAIN ST Unit: 5TH FLR
Project NameROYAL PLAZA
Customer NumberRP 6
ePlanReview 
Description
This fire alarm permit is to install smoke detection and fire alarm system notification appliances in a new 5th floor corridor at the Royal Plaza Building. Building Permit BLD06-03528 is to construct a 1,461 square foot 1-hr fire-resistance-rated egress corridor system to serve residential condominium units located on the 5th story of a high-rise building. Work is to include 1-hr fire-resistance-rated corridor walls, corridor doors having a fire-protection-rating of 20 minutes, suspended ceilings, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/22/20081/22/20081/22/2008PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Alarm Testing1/21/20081/22/20081/22/2008APASS
DetailsForrest France
Required corrections listed at the previous inspection verified for completion, fire alarm testing passed.
INSP-Final Inspection1/18/20081/18/20081/18/2008PFAIL
DetailsForrest France
Need to change descriptor for the smoke detector at the electrical closet, , damper at suite 504 did not close upon actuation of the ID detector, addresses at the in duct detectors for the shell and core devices between units 501 and 502 are not accurate (duplicated elsewhere).
FIR-Aging Inspection12/3/200712/3/200712/3/2007 DEFR
DetailsForrest France
wip