Permit Information
Permit NumberFIR07-00484
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 7701 NORTHVIEW
Project NameFairmont Park Elementary
Customer Number 
ePlanReview 
Description
Scope of Work: Under Ground Only
Beginning from an existing 6” C900 line stubbed in from the street off of W. Northview Street, continue the 6” out 146’ Lf. and stub up into the riser room of the new 57,367-ft/2 bldg. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD06-03277.
Scheduling Inspections:
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/26/20086/26/20086/26/2008PPASS
DetailsForrest France
Under ground completed. As per Troys inspections.
INSP-Sprinkler Rough-in/Hydro1/29/20081/30/20081/30/2008PPASS
DetailsTroy Cobbley
The underground hydro test passed.
INSP-Sprinkler Rough-in7/5/20077/5/20077/5/2007PPASS
DetailsTroy Cobbley
The underground supply line is now ok to bury. The connection to united water still needs to be done.
INSP-Sprinkler Rough-in7/2/20077/3/20077/3/2007AFAIL
DetailsTroy Cobbley
The bury depth of the underground piping does not meet the minumum 4'6" bury depth. Since the next inspection will be the third I have applied a re-inspection fee
INSP-Sprinkler Rough-in6/29/20077/2/20077/2/2007AFAIL
DetailsTroy Cobbley
The underground supply piping has been covered with bedding. I can't see pipe size, tracer wire or the two additional thrust blocks that have been pored. Pipe needs to be uncovered.