Permit Information
Permit NumberFIR07-00485
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 495 S CAPITOL BLVD
Project NameBODO BLDG #8
Customer Number 
ePlanReview 
Description
The Permitted Work Scope:
Modify the existing shell protection by dropping 67 Dry Pendants into a new wall and ceiling layout at the garage level. The heads are being supplied from a Dry pipe system. The existing up-right protection is to remain. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00642.
When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/13/20078/13/20078/13/2007PPASS
DetailsForrest France
Fire sprinkler final inspection passed, permit finaled.
INSP-Sprinkler Rough-in/Hydro6/19/20076/19/20076/19/2007PPART
DetailsForrest France
Approved dry system modifications for cover, noted four plugged tees which will need reconfigured to avoid water collection and freeze potential.