Permit Information
Permit NumberFIR07-00501
StatusFinaled
Name DELTA FIRE SYSTEMS
Site Address 1402 W GROVE ST
Project NameLINEN BUILDING-SHELL
Customer Number 
ePlanReview 
Description
Beginning from the first flange above finished floor, install a wet pipe sprinkler system to serve through out the new 2 story 11,568-ft/2 bldg. The system will be controlled from a wall PIV.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-00500.09/18/07 Revised Scope of Work:
Bin addition to the original scope, sprinkler coverage was added in both stairwells. High temp heads are approved for use in the Basement only.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20079/20/20079/20/2007APASS
DetailsForrest France
Noted items at the previous inspection have been verified for completion, fire sprinkler permit finaled.
INSP-Sprinkler Rough-in/Hydro9/5/20079/6/20079/6/2007APART
DetailsForrest France
OH hydrostatic test passed. No occupancy is allowed prior to the issuance of a certificate of occupancy for the building per conditon of the issued project permits.
INSP-Final Inspection9/4/20079/5/20079/5/2007ANR
DetailsForrest France
Project is not ready for inspection, OH was not pressurized for a hydrostatic test at the time of site visit, rescheduled per conversation with contractor, also need to provide approved resubmittals prior to final. NOTE: contacted the general contractor regarding no occupany prior to the issuance of a CO.
INSP-Sprinkler Rough-in/Hydro8/29/20078/30/20078/30/2007ACANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in/Hydro8/28/20078/29/20078/29/2007PCANC
DetailsTroy Cobbley
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
INSP-Sprinkler Rough-in7/19/20077/20/20077/20/2007PPASS
DetailsTroy Cobbley
See the city approved plans for the location where the sprinkler piping can be covered by the hard lids.