Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR07-00502
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 801 W BOEING ST
Project NameLAKE CITY INTERNATIONAL TRUCK
Customer Number 
ePlanReview 
Description
Scope of Work: Under Ground and overhead, submitted separately under this one permit.
Beginning from an existing 8” C900 line in from the street off of W. Boeing ST., run 146’ of 6” C900 out and stub up into the riser room of the new 20,056-ft/2 bldg. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD07-00017.Scope of Work: Overhead system only under this review.
Install a wet pipe system through out the new 20,056-ft/2 structure. The system is designed to protect Ordinary Group II in the Truck Shop. Miscellaneous storage may be stored in a solid pile configuration or on shelves only up to 12’-0”. No rack storage has been reviewed or approved under this permit. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD07-00017. This permit is attached to Under Ground permit # FIR07-00502.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/16/200711/19/200711/19/2007APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection11/16/200711/16/200711/16/2007PPASS
DetailsForrest France
Fire sprinkler permit finaled, contractor to provide SW heads at the head box as agreed.
INSP-Sprinkler Rough-in/Hydro11/6/200711/7/200711/7/2007APART
DetailsForrest France
OH hydrostatic test passed, c/n items from the previous inspection have been completed, noted that no provision has been made at the riser for forward flow testing of the DCVA backflow.
INSP-Sprinkler Rough-in9/5/20079/6/20079/6/2007APART
DetailsForrest France
OH rough-in is approved except as noted or not yet complete-see annotations on stamped plan set including seismic clearance at a 4" riser, overspaced heads due to HVAC, missing head at the janitors room, SW at the overhead doors are not installed at this time.
INSP-Supply line flush8/28/20078/29/20078/29/2007APASS
DetailsTroy Cobbley
Underground supply flush passed.
INSP-Sprinkler Rough-in/Hydro8/28/20078/29/20078/29/2007APASS
DetailsTroy Cobbley
The underground hydro test passed.
INSP-Sprinkler Rough-in7/24/20077/25/20077/25/2007APART
DetailsForrest France
UG fire supply line installation is good for cover.