FIR-Aging Inspection | 9/4/2012 | 9/4/2012 | 9/4/2012 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 4/9/2012 | 4/9/2012 | 4/9/2012 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 11/10/2011 | 11/10/2011 | 11/10/2011 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 6/22/2011 | 6/22/2011 | 6/22/2011 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 3/11/2011 | 3/11/2011 | 3/15/2011 | | NR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 12/22/2010 | 12/22/2010 | 12/22/2010 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 10/22/2010 | 10/22/2010 | 10/28/2010 | | DONE |
Forrest France
|
|
|
Unfinished
|
FIR-Aging Inspection | 8/18/2010 | 8/18/2010 | 8/19/2010 | | DONE |
Forrest France
|
|
|
In progress
|
FIR-Aging Inspection | 6/15/2010 | 6/15/2010 | 6/17/2010 | | DONE |
Forrest France
|
|
|
Site visit confirmed construction in progress, work is incomplete.
|
INSP-Supply line flush | 9/14/2009 | 9/14/2009 | 9/14/2009 | A | PART |
Forrest France
|
|
|
Underground fire supply line and remote FDC piping flush completed acceptable. NOTE: Post indicator valve is below min. 36" above grade per NFPA 13 8.16.1.3.1 and lacks necessary clearance due to an adjacent tree.
|
INSP-Sprinkler Rough-in/Hydro | 9/10/2009 | 9/11/2009 | 9/14/2009 | P | PART |
Forrest France
|
|
|
Underground fire supply line and remote FDC piping hydrostatic testing completed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 9/9/2009 | 9/10/2009 | 9/10/2009 | A | PART |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 9/9/2009 at 4:38:09 PM. Contact: ###-####.
|
INSP-Sprinkler Rough-in/Hydro | 8/26/2009 | 8/27/2009 | 8/28/2009 | P | PART |
Forrest France
|
|
|
See inspection notes per site visit by T. Frost -Ok to cover. However, there is inadequate coverage under the outside canopy on both levels. I advised the fitter that due to the limited water supply it may be inadvisable to cover the piping until a new plan was designed for protection of the outside canopies. The pipe size may be inadequate to supply all of the sidewall sprinklers.
|
INSP-Sprinkler Rough-in/Hydro | 8/25/2009 | 8/26/2009 | 8/26/2009 | P | CANC |
Troy Cobbley
|
|
|
Cancelled due to time constraints.
|
INSP-Conference | 12/8/2008 | 12/8/2008 | 12/8/2008 | P | DONE |
Forrest France
|
|
|
Conversation with contractor regarding PIV location per NFPA 13 8.15.1.1.1.1 and 8.15.1.3 also 8.14.7.1 and IFC 903.3.1.2.1.
|
INSP-Conference | 12/1/2008 | 12/2/2008 | 12/2/2008 | P | DONE |
Forrest France
|
|
|
On site conference regarding project related fire sprinkler work including FDC and PIV locations.
|
FIR-Aging Inspection | 12/6/2007 | 12/6/2007 | 12/6/2007 | | DEFR |
Forrest France
|
|
|
Construction in progress.
|