Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR07-00521
StatusFinaled
Name DELTA FIRE SYSTEMS
Site Address 1111 W JEFFERSON ST Unit: 550
Project NameBOISE - 1111 W JEFFERSON
Customer Number 
ePlanReview 
Description
The Permitted Work Scope: Over Head Only
Add and relocate heads to accommodate a new wall and ceiling layout on the fifth floor of this high rise office bldg. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00842. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/24/20084/25/20084/25/2008APASS
DetailsForrest France
Fire sprinkler permit approved for final per inspection notes completed 7/27/07, doc. finaled.
INSP-Sprinkler Rough-in/Hydro7/26/20077/27/20077/27/2007APASS
DetailsForrest France
OH install passed final inspection.
INSP-Sprinkler Rough-in/Hydro7/19/20077/23/20077/23/2007AFAIL
DetailsForrest France
Hydrostatic test failed due to start pressure below 200 psi, rooms added to the original TI area shall be shown on resubmittals, one overspaced head noted at the exit corridor SW corner, field modifications for the exit corridor fire sprinklers to be shown on as-built plans.
INSP-Sprinkler Rough-in/Hydro7/5/20077/9/20077/9/2007APART
DetailsForrest France
OH rough-in and the hydrostatic test completed acceptable.
INSP-Sprinkler Rough-in/Hydro7/3/20077/6/20077/5/2007ADEFR
DetailsForrest France
Scheduled by a contractor via Hello! on 7/3/2007 at 1:36:18 PM. Contact: ###-####.