Permit NumberFIR07-00523
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1731 S ENTERTAINMENT AVE
Project NameMOSHI MOSHI
Customer Number 
ePlanReview 
Description
for "2" cooking hoods for moshi moshi restaurant
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/21/20076/22/20076/22/2007APASS
DetailsTroy Cobbley
The hood suppression system operated correctly. The air balance is at .025 in the negative and is ok. Two hood are installed with separate manual activation. I found that the hood have been connected to the fire alarm panel prior to having approved drawings. I notified Mike Timmerman. Bar Green is going to install an "eye brow" on the hood since vertical and horizontal distances exceed what is allowed per IMC chapter 507. This will be verified at the building final.
INSP-Conference6/12/20076/12/20076/12/2007PPASS
DetailsTroy Cobbley
I agreed that the placement of the manual pulls for the hood suppression system could be placed at the entrance arch to the west exit door.