Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR07-00524
StatusFinaled
Name MOUNTAIN ALARM
Site Address 3270 S SHOSHONE ST
Project NameMarriott Hotel Hampton Inn
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing Radionics D7112 with an addressable/conventional Radionics (Bosch) D7024 Fire Alarm Control Panel. The explanation for panel replacement is that elevator recall and shutdown requirements were not possible with the existing FACP and a new fire alarm control panel was required. The scope of work includes bring all areas of the buildings fire alarm system in compliance with current 2003 IFC. Including audible visual notification to be installed in several accessible rooms, the addition of several addressable modules, relays, smoke and heat detectors to initiate elevator recall and shutdown functions. The building is fully fire sprinklered and fire sprinkler and HVAC monitoring along with fire smoke damper operation shall be required. Several fire alarm zones will remain as originally installed and will be connected to a conventional board in the new FACP device compatibility is required. No Building Permit is associated with this work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/23/20094/24/20094/24/2009PPASS
DetailsForrest France
SECOND VISIT for failed first inspection items completed today including retest of post indicator valve, retest for non-functional notification devices, testing for mag lock FA interconnection at the main entry doors, checked relocated 3rd floor manual pull stations, adjusted dB levels at ADA and staff restrooms, map at panel, and elevator controls, supervising station signals checked okay. Fire alarm permit finaled.
INSP-Final Inspection4/17/20094/20/20094/20/2009PCANC
DetailsTroy Cobbley
I spoke to TIm about rescheduling this inspection due to a conflict of interest.
INSP-Final Inspection4/10/20094/13/20094/13/2009PCANC
DetailsForrest France
INSP-Final Inspection7/21/20087/21/20087/21/2008AFAIL
DetailsForrest France
See annotations on approved plan set for locations of areas or items in need of correction including 3rd floor MP stations, dB levels at ADA bathrooms and one staff restroom, two non-functional notification devices, PIV tamper self restoring signal per note #7, fire alarm interconnection to the mag locks at the main entry/exit doors, provide map at the panel per review note #24. FACP batteries, phone lines, sd, HD at the mech. room, sprinkler riser supervision, elevator controls with the exception of hoistway devices and voltage monitoring all tested okay.
FIR-Aging Inspection12/10/200712/10/200712/10/2007 DEFR
DetailsForrest France
Work in progress, pending field inspection request.