Permit Information
Permit NumberFIR07-00525
StatusFinaled
Name MOUNTAIN ALARM
Site Address 3300 S SHOSHONE ST
Project NameMarriott Fairfield Inn
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing Radionics D7112 with an addressable/conventional Radionics (Bosch) D7024 Fire Alarm Control Panel. The explanation for panel replacement is that elevator recall and shutdown requirements were not possible with the existing FACP and a new fire alarm control panel was required. The scope of work includes bring all areas of the buildings fire alarm system in compliance with current 2003 IFC. Including audible visual notification to be installed in several accessible rooms, the addition of several addressable modules, relays, smoke and heat detectors to initiate elevator recall and shutdown functions. The building is fully fire sprinklered and fire sprinkler and HVAC monitoring along with fire smoke damper operation shall be required. Several fire alarm zones will remain as originally installed and will be connected to a conventional board in the new FACP device compatibility is required. No Building Permit is associated with this work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/2/200711/5/200711/5/2007PPASS
DetailsForrest France
Required corrections have been verified for completion, final fire alarm inspection passed, permit finaled.
INSP-Final Inspection10/23/200710/25/200710/26/2007PFAIL
DetailsForrest France
See approved plans 1st floor for areas in need of repair including three SD to be relocated, strobes are not in sync at the pool room, fireman's hat needs to illuminate solid upon activation of the SD at the elevator lobby, need to test EOL, provide signals report at next inspection, noted corrections have been verified from the previous inspection.
INSP-Final Inspection9/7/20079/7/20079/11/2007PDEFR
DetailsForrest France
See inspection comments completed 9/10.
INSP-Final Inspection9/5/20079/6/20079/10/2007ADEFR
DetailsForrest France
See inspection comments on 9/10.
INSP-Final Inspection9/7/20079/10/20079/10/2007AFAIL
DetailsForrest France
Approved plans must be on site per condition of the permit, also need to provide as-builts reflecting field modifications, visible notification appliances in the sleeping areas must meet NFPA 72 7.5.4.4.2., need to provide signage at the doors to the FACP, provide key for the lock at the PIV to enable testing, provide map at the panel. Panel batteries, AC loss, sprinkler monitoring(except PIV) tested okay, verifed signals recieved.
INSP-Final Inspection9/4/20079/5/20079/5/2007ACANC
DetailsForrest France
Overbooked