Permit Information
Permit NumberFIR07-00531
StatusFinaled
Name MR SPRINKLER
Site Address 601 W GOWEN RD
Project NameWESTERN POWER SPORTS
Customer Number 
ePlanReview 
Description
Scope of Work:
Add sprinkler coverage with in the new 24’ high rack storage arrangement and beneath the walkways. The
new racks approved are both single and double row rack type. The new rack sprinklers will be supplied
from the existing system piping. See the limitations of this design on sheet 4 of the report. (Notes 2 – 9) The existing Hose Valve System shall be extended out into the affected area as required.
When fire systems are to be temporarily put out of service, all possible work shall be accomplished in
advance prior to shutting off the water to the fire sprinkler system, so that final connections can be made
quickly and protection restored promptly. The chief (Fire Department) shall be notified when any required
fire-protection system is out of service for over an 8- hour period and upon restoration of service. (IFC
903.2.13, 901.7, 901.7.4 and 1413)
The fire sprinkler system work shall comply with the IFC 2003 and the current Factory Mutual Loss Data Sheets 8 & 9 provided, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code.
This permit is attached to building permit: BLD07-02475 as of 10/26/07; (previously was reported to be part of BLD06-01697).
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/5/200711/7/200711/7/2007PPASS
DetailsForrest France
OH hydrostatic testing completed satisfactory, installation is acceptable, noted flexible couplings need to be added at the relocated hose station supply pipes per NFPA 13-see review comments, agreed to verify completion at the life safety final. Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in11/2/200711/8/200711/5/2007PCANC
DetailsForrest France
mikw Phone #: ###-#### Inspection cancelled from web by: Patricia Smith