Permit Information
Permit NumberFIR07-00539
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 5804 W FAIRVIEW AVE
Project NameCAROLS DESIGN HOUSE
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new fire alarm system in a completely remodeled building. The system includes a fire alarm panel, smoke detector, sprinkler monitoring devices, manual pull station, HVAC monitoring, inside horn, remote annunciator and outside horn strobe. Building Permit BLD07-00913 To completely remodel the interior and exterior of an existing 22,500 sq.ft. retail building for new interior design tenant with supporting storage and office areas per approved plans and DRH07-00159. Work to include, construction of new interior partitions, installation of new exterior glazing, construction of two accessible restrooms, installation of new suspended ceiling and related lighting, new HVAC system, and miscellaneous related interior improvements. Exterior work includes changes to site changes to parking lot and landscaping. This building is fully fire sprinkled for area increase. RmH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing8/30/20078/31/20078/31/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing8/29/20078/30/20078/30/2007ACANC
DetailsForrest France
Overbooked
INSP-Alarm Testing8/27/20078/28/20078/28/2007AFAIL
DetailsTroy Cobbley
The previous correction notice still stands. The monometer test did not pass.
INSP-Alarm Testing8/20/20078/21/20078/21/2007AFAIL
DetailsTroy Cobbley
Lower the pull station, provide manometer testing for the four units on the roof and the two west units below the deck, drill holes in the roof top duct detector housings and test these four duct smoke detectors.