Permit Information
Permit NumberFIR07-00540
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 970 W RIVER ST
Project NameIDAHO RECORDS MGMT BLDG B
Customer Number 
ePlanReview 
Description
This fire alarm permit is to release a preaction sprinkler system solenoid with a fire suppression panel output. The preaction sprinkler system is arranged as a double interlock system using the suppression system smoke detectors and sprinkler low alarm monitored by the fire suppression panel to release the pre action solenoid. Building permit BLD07-00354 is to construct approximately 170 lineal feet of 8 inch reinforced, solid grouted, concrete block interior walls. The masonry walls are constructed to the underside of the existing concrete mezzanine floor level. The concrete walls will create a new 3,490 square foot Outer Storage Vault #B102 and a new 610 square foot Inner Storage Vault #B102A. These vaults will be located at the east end of existing storage building #B. All construction shall be per the approved plans. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/26/20077/27/20077/27/2007APASS
DetailsForrest France
C/N items are completed, fire alarm permit finaled.
INSP-Final Inspection7/26/20077/26/20077/26/2007PCANC
DetailsForrest France
No time available to complete this inspection.
INSP-Final Inspection7/25/20077/25/20077/25/2007PPART
DetailsForrest France
Final pending as-built plans for field modifications, also need to test door holder interconnections when completed, provide updated map at the panel.
INSP-Final Inspection7/23/20077/24/20077/24/2007ANR
DetailsForrest France
Project is not ready for inspection at this time due to fire sprinkler permit testing.
INSP-Final Inspection7/19/20077/20/20077/20/2007PFAIL
DetailsTroy Cobbley
The releasing panel would not trip the valve. The required second permit for the two panel interconnecton was not called in and was not tested. I did test the some of the smoke detectors and all of the manual pulls. But this test really should be started over.