Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR07-00561
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 7009 W FRANKLIN RD
Project NameBISHOP KELLY HIGH SCHOOL
Customer Number 
ePlanReview 
Description
The Permitted Work Scope:
This scope is limited to adding new branch-lines and quick response heads through out the class rooms and hallways to meet code requirements. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00680
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/21/20078/22/20078/22/2007APASS
DetailsTroy Cobbley
Permit is finaled
INSP-Sprinkler Rough-in/Hydro8/20/20078/21/20078/21/2007ACANC
DetailsTroy Cobbley
No time to make a return trip today
INSP-Final Inspection8/20/20078/21/20078/21/2007PCANC
DetailsTroy Cobbley
dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in8/20/20078/21/20078/21/2007AFAIL
DetailsTroy Cobbley
See the city approved plans for painted head, obstruction and hanging insulation problems
INSP-Sprinkler Rough-in7/31/20078/1/20078/1/2007PFAIL
DetailsTroy Cobbley
Mike wanted the piping above the soffit to be inspected but I found that the 2 1/2" piping on the plan is actually 3" piping in the field. Also it appears the piping running back to the riser may be a different size. Also per the fire sprinkler contractor alot of heads have added and as-builts have been submitted but this main size issue has not been reflected on the as-built plans.