Permit NumberFIR07-00575
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 500 S MARDEN LN
Project Name 
Customer Number 
ePlanReview 
Description
Scope of Work:
Beginning from an existing 4” main run a 3” looped system out to serve though out the office area. The loop will also supply an auxiliary Double Interlock Pre-Action system serving the Sever and Control rooms. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any building permit.Revised Scope of Work: 08/16/07
The contractor substituted a single interlock type of pre-action valve and trim package. Supporting material data sheet have been reviewed and are approved. No other apparent changes were made to the plan.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/11/20083/12/20083/12/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro10/31/200711/1/200711/1/2007APART
DetailsForrest France
24 hr. air test for the preaction system passed, overhead install is approved for cover at the drop ceilings with the exception of two noted locations which will need coverage adjustment-see approved plans for annotations.
INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007APART
DetailsForrest France
Begin pneumatic testing of the preaction system at 12:00 @ 46psig.
INSP-Sprinkler Rough-in/Hydro10/29/200710/30/200710/31/2007PPART
DetailsForrest France
OH hydrostatic test completed for both the wet and preaction systems.