Permit NumberFIR07-00603
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3681 S T K AVE
Project NameKEYSTONE AUTO - RACKING
Customer Number 
ePlanReview 
Description
Beginning from an existing 4" supply at the riser, run 180' of 4" out to a new rack system on the south side of the existing structure. The new in-rack sprinkler piping on one level combines with the required flow at the existing roof system. The new design is to protect Group A plastics / Class IV commodity to 20'-0" ht in-rack.
This building is fully fire sprinklered for area increase. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The BLD attached is BLD07-01403.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/20/20078/21/20078/21/2007APASS
DetailsForrest France
Correction items are complete, fire sprinkler permit finaled.
INSP-Final Inspection8/16/20078/17/20078/17/2007AFAIL
DetailsForrest France
Need to fire stop locations where the new main and hose valve piping pass through the riser room walls to maintain the 1hr. rating, missing hangers at one piece of new 4" main, the flow switch has been left mechanicaly disabled and needs to be put back into service immediately-notified contractor this is to be done ASAP.



INSP-Final Inspection8/15/20078/16/20078/16/2007ACANC
DetailsForrest France
Overbooked, no time available for this inspection today.
INSP-Sprinkler Rough-in8/15/20078/16/20078/16/2007ACANC
DetailsForrest France
Overbooked, no time available for this inspection today.