INSP-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 | A | PASS |
Forrest France
|
|
|
Correction items are complete, fire sprinkler permit finaled.
|
INSP-Final Inspection | 8/16/2007 | 8/17/2007 | 8/17/2007 | A | FAIL |
Forrest France
|
|
|
Need to fire stop locations where the new main and hose valve piping pass through the riser room walls to maintain the 1hr. rating, missing hangers at one piece of new 4" main, the flow switch has been left mechanicaly disabled and needs to be put back into service immediately-notified contractor this is to be done ASAP.
|
INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 | A | CANC |
Forrest France
|
|
|
Overbooked, no time available for this inspection today.
|
INSP-Sprinkler Rough-in | 8/15/2007 | 8/16/2007 | 8/16/2007 | A | CANC |
Forrest France
|
|
|
Overbooked, no time available for this inspection today.
|