INSP-Final Inspection | 9/18/2007 | 9/18/2007 | 9/18/2007 | P | PASS |
Forrest France
|
|
|
Required changes have been completed, some issues repaired while on site, signals verified, fire alarm permit finaled.
|
INSP-Final Inspection | 9/14/2007 | 9/17/2007 | 9/17/2007 | A | FAIL |
Forrest France
|
|
|
The duct detector vent tubes are not installed correctly.
|
INSP-Final Inspection | 9/13/2007 | 9/14/2007 | 9/14/2007 | A | FAIL |
Forrest France
|
|
|
Final pending correct installation of the duct detectors.
|
INSP-Final Inspection | 9/12/2007 | 9/13/2007 | 9/13/2007 | A | PART |
Forrest France
|
|
|
Nac panel, SD at panel, a/v notification devices tested okay, one cd rating corrected while on site, random check of the duct detectors revealed incorrect sample tubes and non-approved locations, final pending acceptable installation and testing of the duct detectors.
|
INSP-Final Inspection | 9/11/2007 | 9/12/2007 | 9/12/2007 | P | CANC |
Forrest France
|
|
|
Overbooked.
|