INSP-Final Inspection | 9/24/2007 | 9/24/2007 | 9/24/2007 | P | PASS |
Forrest France
|
|
|
Fire sprinkler passed final inspection, permit finaled.
|
INSP-Sprinkler Rough-in | 9/19/2007 | 9/20/2007 | 9/20/2007 | A | PART |
Forrest France
|
|
|
Remainder of the overhead rough-in is approved for cover as noted on stamped plan set.
|
INSP-Sprinkler Rough-in | 9/19/2007 | 9/19/2007 | 9/20/2007 | P | CANC |
Forrest France
|
|
|
Overbooked.
|
INSP-Sprinkler Rough-in | 9/11/2007 | 9/12/2007 | 9/12/2007 | A | PART |
Forrest France
|
|
|
See approved plans for areas okay for cover at the hard lid ceilings.
|
INSP-Sprinkler Rough-in | 8/29/2007 | 8/30/2007 | 8/30/2007 | A | PART |
Forrest France
|
|
|
Required corrections noted at the previous inspection have been repaired, OH fire sprinkler modifications for phase one as noted on approved plans are okay for ceiling cover.
|
INSP-Sprinkler Rough-in | 8/29/2007 | 8/29/2007 | 8/29/2007 | P | CANC |
Troy Cobbley
|
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
INSP-Sprinkler Rough-in | 8/22/2007 | 8/23/2007 | 8/23/2007 | A | FAIL |
Forrest France
|
|
|
See approved plans for areas inspected and noted defficiences including overspaced heads at an office and equip. room, missing hangers at two arm-overs, and missing heads at three closets.
|