INSP-Final Inspection | 11/1/2007 | 11/1/2007 | 11/2/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | FAIL |
Troy Cobbley
|
|
|
401canopies need to be installed in the restrooms where lights are blocking pendant heads. One head needs to be added at a fixture on the sales floor and two heads are located too close to one another at another fixture on the sales floor. Plans need to be resubmitted to the city of boise due to the amount of added heads caused by the fixtures. The scope of work calls for the air compressor to be changed out which has not been done yet.
|
INSP-Sprinkler Rough-in | 10/17/2007 | 10/18/2007 | 10/18/2007 | A | PASS |
Troy Cobbley
|
|
|
The sprinkler piping in areas 16, 17 & 18 is ok to cover.
|
INSP-Sprinkler Rough-in | 10/15/2007 | 10/16/2007 | 10/16/2007 | P | PASS |
Troy Cobbley
|
|
|
Sales floor - areas 12 & 13 are ok to cover
|
INSP-Sprinkler Rough-in | 9/27/2007 | 9/28/2007 | 9/28/2007 | P | PASS |
Troy Cobbley
|
|
|
See the city approved plans for areas marked with todays date that are ok for cover.
|
INSP-Sprinkler Rough-in | 9/11/2007 | 9/12/2007 | 9/12/2007 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for piping in the womens clothing area that is ok to cover.
|
INSP-Sprinkler Rough-in | 9/7/2007 | 9/10/2007 | 9/10/2007 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for the men's restroom but the fire sprinkler contractor did not have the approved plans. We went to the bakery and I showed him the overspaced heads there.
|
INSP-Sprinkler Rough-in | 8/30/2007 | 8/31/2007 | 8/31/2007 | A | PASS |
Troy Cobbley
|
|
|
This rough to cover is for areas 7&8. Piping is ok to cover. See the city approved plans for the location with todays date.
|
INSP-Sprinkler Rough-in | 8/29/2007 | 8/30/2007 | 8/30/2007 | A | CANC |
Forrest France
|
|
|
Overbooked
|
INSP-Sprinkler Rough-in | 8/22/2007 | 8/23/2007 | 8/23/2007 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for locations where the piping is ok to cover marked with todays date.
|
INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 | A | FAIL |
Troy Cobbley
|
|
|
This inspection was just for the electronics area and for part of the womens clothing department. See the city approved plans for the exact locations.
|
INSP-Final Inspection | 8/15/2007 | 8/15/2007 | 8/15/2007 | P | CANC |
Troy Cobbley
|
|
|
Duplicate inspection. See previous entry.
|
INSP-Sprinkler Rough-in | 8/15/2007 | 8/15/2007 | 8/15/2007 | P | FAIL |
Troy Cobbley
|
|
|
This inspection was for the electronics area only. I found six missing sprinkler heads. See the city approved fire sprinkler plans for locations.
|