Permit Information
Permit NumberFIR07-00642
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 10751 W OVERLAND RD
Project NameFRED MEYER
Customer Number 
ePlanReview 
Description
The Permitted Work Scope: Over Head Only
Modify the existing system by adding, removing and relocating heads to accommodate a new wall and ceiling layout in the Electronics area. On the sales floor, heads will be cut back and relocated into a new elevated grid. This review is limited to the interior of the project as described in the BLD permit scope. There were no overhead doors or exterior work associated with the future Garden Center expansion submitted under this review.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00948. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/1/200711/1/200711/2/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/30/200710/31/200710/31/2007AFAIL
DetailsTroy Cobbley
401canopies need to be installed in the restrooms where lights are blocking pendant heads. One head needs to be added at a fixture on the sales floor and two heads are located too close to one another at another fixture on the sales floor. Plans need to be resubmitted to the city of boise due to the amount of added heads caused by the fixtures. The scope of work calls for the air compressor to be changed out which has not been done yet.
INSP-Sprinkler Rough-in10/17/200710/18/200710/18/2007APASS
DetailsTroy Cobbley
The sprinkler piping in areas 16, 17 & 18 is ok to cover.
INSP-Sprinkler Rough-in10/15/200710/16/200710/16/2007PPASS
DetailsTroy Cobbley
Sales floor - areas 12 & 13 are ok to cover
INSP-Sprinkler Rough-in9/27/20079/28/20079/28/2007PPASS
DetailsTroy Cobbley
See the city approved plans for areas marked with todays date that are ok for cover.
INSP-Sprinkler Rough-in9/11/20079/12/20079/12/2007APASS
DetailsTroy Cobbley
See the city approved plans for piping in the womens clothing area that is ok to cover.
INSP-Sprinkler Rough-in9/7/20079/10/20079/10/2007AFAIL
DetailsTroy Cobbley
Inspection was for the men's restroom but the fire sprinkler contractor did not have the approved plans. We went to the bakery and I showed him the overspaced heads there.
INSP-Sprinkler Rough-in8/30/20078/31/20078/31/2007APASS
DetailsTroy Cobbley
This rough to cover is for areas 7&8. Piping is ok to cover. See the city approved plans for the location with todays date.
INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007ACANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in8/22/20078/23/20078/23/2007APASS
DetailsTroy Cobbley
See the city approved plans for locations where the piping is ok to cover marked with todays date.
INSP-Final Inspection8/15/20078/16/20078/16/2007AFAIL
DetailsTroy Cobbley
This inspection was just for the electronics area and for part of the womens clothing department. See the city approved plans for the exact locations.
INSP-Final Inspection8/15/20078/15/20078/15/2007PCANC
DetailsTroy Cobbley
Duplicate inspection. See previous entry.
INSP-Sprinkler Rough-in8/15/20078/15/20078/15/2007PFAIL
DetailsTroy Cobbley
This inspection was for the electronics area only. I found six missing sprinkler heads. See the city approved fire sprinkler plans for locations.