Permit NumberFIR07-00662
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 1455 S CAPITOL BLVD
Project NameMarriott Towne Place Suites
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new fire alarm system in a new 123 unit hotel. The system includes required manual fire alarm, automatic smoke detection, in room system detectors used as smoke alarms, elevator recall and shut down, fire smoke damper control and audible visual notification. Building Permit BLD06-00456 is to construct a new 72,923 square feet, four story, wood framed, 123 unit motel with approximately 14,838 square feet for support area for meeting rooms, indoor swimming pool and spa, lobby with prep kitchen and 820 square feet of covered entry and patio area. NOTE: This building is required to have a NFPA 13 Fire Sprinkler system used for area increase. This permit does not include the interior swimming pool, spa and related pool equipment. A separate permit with approvals will be required prior to swimming pool construction. All construction shall be per the approved plans and attached comment list. Note: Grading issued under BLD06-01822. MJP DRH 05-00277 CUP 05-55565 CVA05-00020

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/12/20082/12/20082/12/2008APASS
DetailsForrest France
Fire alarm work passed final inspection, permit finaled.
INSP-Alarm Testing2/6/20082/7/20082/7/2008APASS
DetailsForrest France
Completed balance of fire alarm testing including initiation devices on the 3rd and 4th floors, dampers at all floors-(non-functional dampers at the west end floors 1-4 repaired while on site), elevator recall, EOL voltage, closure at one door repaired while on site, signals and account checked, and reinspected noted defficiencies from the previous day for compliance. Need to provide building map at the panel including all initiation devices and their locations per review notes and as discussed, fire alarm permit work approved for final.
INSP-Alarm Testing2/5/20082/6/20082/6/2008APART
DetailsForrest France
Corrections noted at the previous inspection including a/v and pull station locations and non-functional sounder bases at three rooms verified for completion. FACP phone lines, batteries, AC power, SD above panel, and first floor nac tested okay. Notification devices for the 1st thru 4th floors tested - noted lacking coverage at the first floor vending/ice room, dB above 110 at two public restrooms (corrected while on site), a/v at the maintenance managers office on the 3rd floor does not function, sounder bases at three rooms 236, 336,and 436 do not function on general alarm. Also tested initating devices for the 1st and 2nd floors (manual pull stations and SD's only). Need to provide access for visual inspection of FSD functionality at some areas. Still need to test 3rd and 4th floor alarm initiation, elevator recall at both cars, 3rd and 4th floor nac panels, and check account and signal reciept information.
INSP-Alarm Testing1/29/20081/30/20081/30/2008ADEFR
DetailsForrest France
Talk to Rand with Alarm Star About the issues of A/V devices being to low. Pull stations to high and the wrong (CD) for the devices in th ADA rooms.KR
INSP-Alarm Testing1/28/20081/29/20081/29/2008AFAIL
DetailsForrest France
See inspection notes per site visit completed by K. Roule.
FIR-Aging Inspection12/14/200712/14/200712/14/2007 DEFR
DetailsForrest France
Under construction, work in progress.