Permit Information
Permit NumberFIR07-00663
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1908 N 13TH ST
Project NameASHLEY MANOR
Customer Number 
ePlanReview 
Description
Scope of Work: Overhead Only
Beginning from the supply side of the back flow device, (provided by others) Install a new fire sprinkler system through out the one story 2,450-ft/a assisted living home. System shall be equipped with an alarm initiating device and an outside alarm. The plans shall include coverage in the garage, closets, bathrooms and foyers as directed by the bldg. department. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is not attached a BLD permit.
08/16/07 Plan Review Comments:05/22/08 Revised Scope of Work: The underground was revised along with the calculations to omit a water meter as it was not required.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/200810/14/200810/14/2008APASS
DetailsForrest France
All corrections made per last inspection. KR
INSP-Final Inspection9/17/20089/18/20089/18/2008AFAIL
DetailsForrest France
Per contractor missing cold cavity protection, noted missing escutcheons, lacking tamper switches at the main control and backflow shutoff valves.
INSP-Sprinkler Rough-in/Hydro6/12/20086/12/20086/12/2008PPART
DetailsForrest France
Final pending system fire alarm interconnection.
INSP-Sprinkler Rough-in/Hydro6/2/20086/3/20086/3/2008APART
DetailsForrest France
Overhead hydrostatic testing completed satisfactory for the new system piping.
INSP-Sprinkler Rough-in5/29/20086/2/20086/2/2008APASS
DetailsTroy Cobbley
UG Flush and the forward flush passed.. I notified todd that the flow switch and tamper switches will need to be connected to the fire alarm system.
INSP-Sprinkler Rough-in5/15/20085/15/20085/15/2008PPART
DetailsForrest France
Okay to cover underground supply line. Agreed to accept as-built plans for the deletion of the meter due to dedicated fire service.
INSP-Sprinkler Rough-in5/9/20085/9/20085/9/2008PFAIL
DetailsForrest France
UG fire supply line is not approved for cover due to missing meter installation per plan, depth of bury does not meet min. requirements adjacent to the foundation.
INSP-Sprinkler Rough-in/Hydro12/13/200712/13/200712/13/2007PPART
DetailsForrest France
Missing one head at the pantry, remainder of the OH rough-in is acceptable, riser is not yet built, need to provide cold cavity protection as detailed.