Permit NumberFIR07-00664
StatusFinaled
Name R M E INC
Site Address 105 N 9TH ST
Project NameSONNA BLDG
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new fire alarm system in an existing building. The fire alarm system will include smoke detector above FACP, HVAC monitoring and audible visual notification. Application indicates that sprinkler flow and valve tampers are to remain on the existing basement dialer/basement FACP. Building Permit BLD07-00845 is to perform interior and minor exterior work to expand an existing 1,653 sq.ft. office into an adjacent 2067 square feet retail space to bring the office to 3,760 square feet. To relocate the existing store front entry door to make an accessible entrance. NOTE: This building is fully fire sprinklered for substitution of one-hour fire-resistive construction. All construction shall be per the approved plans and attached comment list. CZC07-00076. MJP
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/24/20079/24/20079/24/2007PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection9/20/20079/21/20079/21/2007PNR
DetailsForrest France
Need NFPA 72 record of completion forms.
INSP-Alarm Testing9/5/20079/5/20079/6/2007PPART
DetailsForrest France
Noted corrections have been made, fire alarm testing passed, final pending completion of the scope of work per building plans and removal of the old FACP no longer in service adjacent to the fire riser.
INSP-Alarm Testing9/4/20079/5/20079/5/2007ACANC
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
INSP-Alarm Testing8/31/20079/4/20079/4/2007AFAIL
DetailsForrest France
The SD at the new control panel is too close to an HVAC supply register, one duct detector has the sample tube installed backward, need to locate the inspectors test valve to enable testing of the sprinkler flow switch, the existing FACP if no longer in service shall be removed to prevent confusion, need to verify signals at the supervising station.
INSP-Alarm Testing8/30/20078/31/20078/31/2007ACANC
DetailsForrest France
Overbooked