Permit Information
Permit NumberFIR07-00671
StatusFinaled
Name ECS
Site Address 7200 W BARRISTER DR
Project NameAda County Jail FACP Replaceme
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace the existing outdated Edwards IRC3 fire alarm control panel at the Main ADA County Jail Facility and replace it with an Edwards EST3 network fire alarm panel that will be directly compatible with the jails pod C and new medical unit FACP's and their devices. New audible visual notification is required in support and public accessible areas. Staff notification within the facility will be allowed to be accomplished using existing fire alarm emergency procedures and use of the jails radio communications. The existing central jail initiating devices are to be reused and are to be compatible with the new FACP. New control switches and status indication (LEDs) will be part of the new FACP and used for jail smoke control and HVAC control status indication. Existing smoke control sequences and indication for the main jail HVAC units will not change from the original conditions. The new Medical Unit smoke control sequence will be as required and approved by the building department and building permit BLD06-03515 and Fire Alarm Permit FIR07-00380. No building permit is directly associated with this work. However, this permit must be completed prior to fire alarm permit FIR07-00380 being finaled.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/200711/14/200711/14/2007PPASS
DetailsTroy Cobbley
permit finaled per mike timmerman
INSP-Final Inspection10/30/200710/31/200710/31/2007ADONE
DetailsTroy Cobbley
See mike timmermans notes for items tested.
INSP-Final Inspection10/30/200710/30/200710/31/2007PFAIL
DetailsTroy Cobbley
See mike timmermans notes for items tested and corrections needed.
INSP-Final Inspection10/25/200710/26/200710/26/2007AFAIL
DetailsTroy Cobbley
See mike timmermans notes for items tested and deficiencies such as the smoke detectors too close to the supply registers and the smoke detectors spaced in the areas where beams are 20" deep.
INSP-Final Inspection10/25/200710/25/200710/26/2007PFAIL
DetailsTroy Cobbley
mike timmerman is working through the inspection. There appear to be deficiencies with the existing devices such as being placed too close to supply diffusers.