Permit Information
Permit NumberFIR07-00674
StatusFinaled
Name MICRON TECHNOLOGY INC FP
Site Address 8000 S FEDERAL WAY
Project Name 
Customer NumberC11265
ePlanReview 
Description
Fire Sprinkler System: C11265 B16 Basement Remodel of CFA Area
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/27/200710/3/200710/3/2007APASS
DetailsForrest France
Required corrections have been completed, fire sprinkler permit finaled.
INSP-Final Inspection9/20/20079/26/20079/26/2007APART
DetailsForrest France
Noted three upright heads at mechanical room 000Y which exceed the max. allowable distance below the deck for proper response time- the mech. piping above the heads does not provide adequate heat collection. The remainder of overhead installation is acceptable.
INSP-Final Inspection9/18/20079/21/20079/20/2007PCANC
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
INSP-Final Inspection9/17/20079/19/20079/18/2007ACANC
DetailsForrest France
complete fire sprinkler inspection. Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
INSP-Sprinkler Rough-in/Hydro8/27/20078/29/20078/29/2007AFAIL
DetailsTroy Cobbley
Provide verification that the 1/2" piping to the sprinkler heads and the tape separation on the piping/hangers was allowed under the code in which the buidling was built. See the city approved plans for locations where sprinkler heads need to be changed from 200 to 155 degrees. Also see the plans where the clouded area is the only area not inspected.