Permit Information
Permit NumberFIR07-00704
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3795 S DEVELOPMENT AVE Unit: 100
Project NameSYRINGA NETWORKS
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing non required fire alarm and sprinkler monitoring system and install a new addressable non required manual fire alarm system with full audible visual notification in a tenant space within the building. The new fire alarm panel will consist of sprinkler and suppression system monitoring installed in the switch gear and equipment room. New manual pull stations will be installed in the Syringa Network tenant space and in the common corridor exits. A smoke detector will be installed above the new FACP. 12-14-2007 Plan Modification - This plan modification includes removing the original Ansul suppression panel that was to be installed for suppression system releasing service and use the main building FACP and releasing "SRPPs" modules that are connected to the main building fire alarm system for fire suppression and sprinkler pre-action releasing service. All releasing service requirements will be initiated by the building fire alarm control panel. Additional fire suppression peripheral devices are now shown on the building floor plans and riser along with the suppression area smoke detectors that will be used for cross zoning and a double interlock pre-action system. - No building permit is associated with this work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/25/20082/27/20082/28/2008PPASS
DetailsForrest France
Corrections verified for completion, final alarm testing passed, permit finaled.
INSP-Final Inspection2/13/20082/15/20082/15/2008PFAIL
DetailsForrest France
Completed test of new fire alarm panel. Found that strobes in corridors were not in-sync and existing strobes in hallways were at 79 inches. As per Sam no changes will need to be made to existing strobes.All other testing per permit Final.
FIR-Aging Inspection1/8/20081/8/20081/8/2008 DEFR
DetailsForrest France
Work in progress