Permit NumberFIR07-00728
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 641 W MCGREGOR DR Unit: 100
Project NameFederal Way Commerce - #3
Customer Number 
ePlanReview 
Description
The Permitted Work Scope: Over Head Only
Modify the existing system by adding and relocating heads to accommodate a new wall and ceiling layout in suite100. In addition heads will be added and relocated @ col. # 5 in the warehouse to accommodate a new demising wall. A single HSW will be added beneath a new OH door at
Col. # 3. This review is limited to the interior of the project as it is clouded for reference with no project revision notes dated 08/21/2007.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-01648. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/18/200710/19/200710/19/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection10/18/200710/18/200710/18/2007PFAIL
DetailsTroy Cobbley
The head in the warehouse restroom is still covered and appears to be textured and painted.
INSP-Sprinkler Rough-in10/3/200710/4/200710/5/2007PPART
DetailsForrest France
OH install is good for cover at the drop ceilings, one head at the warehouse restroom is covered, the SW head at the overhead door in not required due to door configuration, final pending ceiling tile and escutcheons.
INSP-Sprinkler Rough-in10/3/200710/4/200710/3/2007PCANC
DetailsForrest France
OH Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley