Permit Information
Permit NumberFIR07-00770
StatusFinaled
Name SUMMIT SECURITY SYSTEMS
Site Address 10751 W OVERLAND RD
Project NameFRED MEYER
Customer Number 
ePlanReview 
Description
This fire alarm permit is to upgrade the existing fire alarm sprinkler monitoring panel to provide for a new garden center expansion and provide audible visual notification throughout the store. Building permit BLD07-00948 work includes selective demolition to prepare for new interior layout and finishes for existing sales floor display and customer service areas of 169,458 sq. ft. main floor and preparation of Garden Center area for construction of a 3,000 sq. ft. cover with support structure and expansion of the outdoor garden/sales area to become 8,871 sq. ft. To construct a new wall to create a new 1,440 sq. ft. (1,392 interior) merchandise pick-up area; add a new loading platform, stairs and rails in the dock area from existing storage area; add a new overhead door to the garden sales/display area and man door as an exit directly to the exterior along the exterior side of new fenced in garden open sales site from the new MPA. To upgrade interior ceilings, floors and wall finishes; display fixtures, freezers, coolers, display and service counters; upgrade bakery equipment and relocate Type I hood with protected grease duct exhaust system; upgrade electrical, mechanical and plumbing; replace interior and exterior doors as indicated, all per approved plans. DRH07-00150 & CFH07-00015. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/18/200712/19/200712/19/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection12/12/200712/13/200712/13/2007AFAIL
DetailsTroy Cobbley
I arrived at the scheduled 8:00am and found tim but no heating guy. I left and returned at 11:45am. After testing four of the five duct smoke detectors in the open sales area, one duct detector was found inoperative. The test was stopped due to time constraints.
INSP-Final Inspection11/26/200711/27/200711/27/2007AFAIL
DetailsTroy Cobbley
The duct smoke detectors still need to be tested. Per tim not all of the units are shutting down upon detection of smoke. The notification circuits have been repaired and tested. The smoke detectors located over the nac panels have been relocated to the deck and tested.
INSP-Alarm Testing11/15/200711/20/200711/20/2007ADONE
DetailsTroy Cobbley
The alarm at the garden center dry system has been repaired. The secondary phone line trouble restoral has been repaired. The audio/visual have been tested. Not all of the exterior tenant devices are operating. The audio/visual at the north east entrance is not operating. The a/v in the bakery needs relocated as per the plan. I need to spot check the high ceiling a/v's to verify candella compliance. The smoke detectors over the nac panels need located per code at the deck as discussed and tested. None of the duct smoke detectors were tested since the contractor did not have smoke. One hvac unit at the very west end of the store does not have a duct smoke detector as shown on the plans. The duct detectors in the outside tenants are not installed either. As-builts are required.
INSP-Alarm Testing11/15/200711/19/200711/19/2007ADONE
DetailsTroy Cobbley
Need to test all audio/visuals, test duct smoke detectors and the flow alarm on the new dry pipe vavle did not sen a signal to the facp. I also need a print out of todays signals for verification.
INSP-Alarm Testing11/15/200711/16/200711/16/2007ADONE
DetailsTroy Cobbley
The ham hood system came in and went out correctly. The phone lines also tested ok. But the phone line troubles do not annunciate audibly at the annunciators and the zone descriptors for the NAC panels is not correct. Battery troubles do not annunciate at the panel either. I believe its a D113 module that needs to be added based on past experiences. This is all that was tested today.