INSP-Final Inspection | 3/31/2008 | 4/7/2008 | 4/7/2008 | P | PASS |
Forrest France
|
|
|
Complete remaining testing per Forrest notes from last inspection.KR
|
INSP-Final Inspection | 3/25/2008 | 3/26/2008 | 3/26/2008 | A | FAIL |
Forrest France
|
|
|
Prior to inspection the NFPA 72 "Inspection and testing" form Fig. 10.6.2.3 must be completed including a copy of the supervising station signals report- see fire code review notes #8, audible notification at the existing tenant URS is not temporal as required, provide key for elevator reset at the next inspection. Manual pull, SD at the panel, sprinkler monitoring, FACP phone lines, batteries, AC loss, and the duct detector tested okay, notification device locations for the first and second floors appear satisfactory. Elevator controls not tested at this tme.
|
FIR-Aging Inspection | 1/31/2008 | 1/31/2008 | 1/31/2008 | | DEFR |
Forrest France
|
|
|
Site work in progress, pending field inspection request.
|