Permit Number | FIR07-00916 |
Status | Finaled |
Name |
ALLIED GENERAL FIRE & SECURITY
|
Site Address |
4724 W STATE ST
|
Project Name | COLLISTER SHOPPING CNTR |
Customer Number | |
ePlanReview | |
Description |
This fire alarm permit is to relocate the existing building FACP, install non required audible visual notification, provide HVAC monitoring at the FACP of two duct smoke detectors and install a remote annunciator. The fire alarm system includes sprinkler water flow, valve tamper switches, PIV, kitchen hood and manual pull station the 2007 NFPA 72 was used so smoke detection above the FACP is not required. Building permit BLD07-01555 is a remodel, changing occupancy from a former retail space to a new 12,169 sq. ft. assembly library tenant with associated office and storage per approved plans and DRH07-00262. This building is a one-hour rated building. (Type V-A Construction) Work to include some interior demolition work, removing portions of the existing front CMU exterior wall, some new structural steel work for new exterior window and door openings at front exterior wall, new interior walls and doors, new interior finish, new restrooms, fire sprinkler and alarm work, mechanical work including some new units, plumbing work, and electrical work. Special Inspection is required for structural steel work/welding and for epoxy/adhesive anchor installations. The west wall of this tenant space is an existing 2-hour rated fire wall with a 30" minimum parapet. Nonseparated Uses per IBC Section 302.3.1. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is fully fire sprinklered for area increase. JCB.
|