INSP-Final Inspection | 5/2/2008 | 5/5/2008 | 5/5/2008 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Storage has been removed from the top of the couch storage bins.
|
INSP-Final Inspection | 5/1/2008 | 5/2/2008 | 5/2/2008 | A | FAIL |
Troy Cobbley
|
|
|
Need the pallets that have been placed on top of the couch storage boxes removed. I let the warehouse manager know that no items can be stored there. The PIV tamper switch needs adjusted so that it reports correctly. The forward flush passed. The trip tests of the two dry systems passed.
|
INSP-Final Inspection | 4/8/2008 | 4/11/2008 | 4/11/2008 | A | CANC |
Troy Cobbley
|
|
|
Per todd the inspection is to be canceled due to the fire alarm system not being ready.
|
INSP-Sprinkler Rough-in/Hydro | 4/2/2008 | 4/3/2008 | 4/3/2008 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test passed
|
INSP-Sprinkler Rough-in | 4/1/2008 | 4/2/2008 | 4/2/2008 | A | PASS |
Troy Cobbley
|
|
|
24hr Air Test started at 8:30 the left system has 45 psi and the right system has 44 psi.
|
INSP-Sprinkler Rough-in/Hydro | 3/28/2008 | 3/31/2008 | 3/31/2008 | A | PASS |
Troy Cobbley
|
|
|
OH Hydro Inspecion passed
|
INSP-Sprinkler Rough-in | 3/26/2008 | 3/28/2008 | 3/28/2008 | A | PART |
Troy Cobbley
|
|
|
The overhead rough-in as far as piping installation is passed. The wrong heads have been installed. The correct sprinkler heads need to be installed or approval from the plan reviewer is required if they are to be left. The hose valves/piping as shown on the city approved plans has been removed as per Dave Hanniman.
|
INSP-Sprinkler Rough-in | 3/26/2008 | 3/27/2008 | 3/27/2008 | A | PASS |
Troy Cobbley
|
|
|
Underground flush passed
|
INSP-Sprinkler Rough-in/Hydro | 3/25/2008 | 3/25/2008 | 3/26/2008 | P | PASS |
Troy Cobbley
|
|
|
UG Hydro Inspection passed for the underground supply and the remote fdc
|
INSP-Sprinkler Rough-in | 3/12/2008 | 3/13/2008 | 3/13/2008 | P | PASS |
Troy Cobbley
|
|
|
The remote FDC piping can be covered.
|
INSP-Sprinkler Rough-in | 3/11/2008 | 3/13/2008 | 3/12/2008 | A | CANC |
Troy Cobbley
|
|
|
UG Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in | 3/10/2008 | 3/11/2008 | 3/11/2008 | P | PASS |
Troy Cobbley
|
|
|
Underground supply piping can be buried. Still need an inspection on the remote FDC piping. I suggested putting in the conduit for the PIV tamper as well prior to bury.
|
FIR-Aging Inspection | 3/5/2008 | 3/5/2008 | 3/7/2008 | | NR |
Troy Cobbley
|
|
|
WIP
|