INSP-Final Inspection | 7/14/2008 | 7/15/2008 | 7/15/2008 | A | PASS |
Forrest France
|
|
|
Chain and lock was added to PIV. New set of resubmitted plans were on site with all corrections made. KR
|
INSP-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 | A | FAIL |
Forrest France
|
|
|
Plans are still under review for resubmittals.Fire sprinkler Inspection completed. One remaining item.Chain and lock is required on PIV. KR
|
INSP-Sprinkler Rough-in/Hydro | 6/20/2008 | 6/20/2008 | 6/20/2008 | P | PART |
Forrest France
|
|
|
Verified some items per the C/N are finished including added heads at the wash bay, added seismic brace, spacing at the compressor room. Noted fire alarm work is nearly complete including tamper and flow switch wiring and FACP installation prior to the issuance of a fire alarm permit. Double permit fees will apply.
|
INSP-Sprinkler Rough-in/Hydro | 6/12/2008 | 6/12/2008 | 6/12/2008 | P | PART |
Forrest France
|
|
|
OH hydrostatic testing for both wet systems passed. OH rough-in failed due to overspaced heads at the wash bay, blocked heads at the compressor room, missing EQ brace at the 4" main NE corner of the warehouse, need to provide resubmittals for pipe size changes at the north office areas, some finish items at the riser are not complete including flex. couplings, FDC ball drip, head box, tagged DCVA, etc.
|
INSP-Sprinkler Rough-in | 5/30/2008 | 6/3/2008 | 6/3/2008 | P | PART |
Forrest France
|
|
|
1st and 2nd floor south offices OH rough-in is approved for cover with the exception of one missing EQ brace at the 2nd floor 3" main east side last piece.
|
INSP-Sprinkler Rough-in | 4/11/2008 | 4/14/2008 | 4/14/2008 | A | PASS |
Troy Cobbley
|
|
|
The restroom, shower & locker room area are ok to cover. See the city approved plans for locations.
|
INSP-Sprinkler Rough-in/Hydro | 3/25/2008 | 3/25/2008 | 3/25/2008 | P | NR |
Forrest France
|
|
|
Not completed for inspection.
|
FIR-Aging Inspection | 3/20/2008 | 3/20/2008 | 3/20/2008 | | DEFR |
Forrest France
|
|
|
Work in progress, construction underway.
|