Permit NumberFIR07-00969
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4554 W AERONCA ST
Project NameSPR-UNG Western Aircraft
Customer Number 
ePlanReview 
Description
TVFP to install 50 LF of new 8" C-900 fire sprinkler supply piping from stub in at property line by United Water. This work is associated with BLD07-01960.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/14/20095/15/20095/14/2009APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection6/13/20086/13/20086/13/2008PFAIL
DetailsTroy Cobbley
The electric alarm bell has not been connected to the fire alarm panel. It has actually been connected to the forward flush control valve. When I operated the valve sparks flew from the junction box. Also the FDC is mounted below 18". Per the plans it was to be installed at 30". Need to perform forward flush as well.
INSP-Sprinkler Rough-in/Hydro4/21/20084/21/20084/21/2008PPASS
DetailsTroy Cobbley
The underground hydro test and flush passed
INSP-Sprinkler Rough-in4/15/20084/15/20084/16/2008PPASS
DetailsTroy Cobbley
The remaining underground is ok to cover
INSP-Sprinkler Rough-in12/4/200712/4/200712/4/2007PPASS
DetailsTroy Cobbley
The underground stub out is ok to cover. The remaining underground piping needs to be inspected when installed.