INSP-Final Inspection | 6/29/2009 | 6/30/2009 | 6/30/2009 | P | PASS |
Forrest France
|
|
|
Correction notice items verified for completion, final site fire alarm testing passed, permit finaled.
|
INSP-Final Inspection | 6/18/2009 | 6/19/2009 | 6/22/2009 | P | PART |
Forrest France
|
|
|
See inspection comments 6/22.
|
INSP-Final Inspection | 6/19/2009 | 6/22/2009 | 6/22/2009 | P | PART |
Forrest France
|
|
|
Items needed for final include adjustment at the PIV tamper switch, program door holds at two locations to release on general alarm conditon, elevator recall functions did not operate correctly. Remainder of installation passed field testing.
|
INSP-Final Inspection | 6/17/2009 | 6/17/2009 | 6/17/2009 | P | PART |
Forrest France
|
|
|
Missing current set of approved plans on site for inspection as requested.
|
INSP-Final Inspection | 6/15/2009 | 6/16/2009 | 6/16/2009 | P | CANC |
Forrest France
|
|
|
ryan - after 2 please Phone #: ###-#### Rescheduled per conversation with contractor.
|
INSP-Final Inspection | 6/11/2009 | 6/12/2009 | 6/12/2009 | P | CANC |
Troy Cobbley
|
|
|
Cancelled per Forrest. To be rescheduled for next week.
|
INSP-Alarm Testing | 5/8/2009 | 5/11/2009 | 5/13/2009 | P | FAIL |
Forrest France
|
|
|
Need to provide NFPA 72 record of inspection and testing including a signals list prior to final on site acceptance test, missing building map at the FACP for device and zone locations, field installation does not match approved plans including sprinkler risers, deleted/added devices, etc., plan resubmittals are necessary to reflect changes, noted some minor field adjustments to be made for spacing of notification devices.
|
INSP-Alarm Testing | 5/6/2009 | 5/7/2009 | 5/7/2009 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 5/6/2009 at 12:19:58 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 7 2009 10:32AM.
|
INSP-Alarm Testing | 4/27/2009 | 4/30/2009 | 4/29/2009 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 4/27/2009 at 4:00:14 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Apr 29 2009 1:32PM.
|
INSP-Alarm Testing | 4/23/2009 | 4/27/2009 | 4/27/2009 | P | NR |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 4/23/2009 at 10:21:08 AM. Contact: ###-####. Contractor not available for site inspection per phone conversation.
|
INSP-Final Inspection | 2/18/2009 | 2/19/2009 | 2/19/2009 | A | DEFR |
Forrest France
|
|
|
Casey- call 30 mins prior to going Phone #: ###-#### * NOTE * Wrong permit number requested by contractor-Intended for project related fire sprinkler work.
|
INSP-Final Inspection | 2/17/2009 | 2/18/2009 | 2/18/2009 | A | CANC |
Forrest France
|
|
|
Jerry- call 30 mins prior to going Phone #: ###-####
|
INSP-Conference | 3/31/2008 | 4/1/2008 | 4/1/2008 | P | CANC |
Forrest France
|
|
|
Wrong permit called in for conference.Will call in correct permit.KR
|