Permit Information
Permit NumberFIR07-00997
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3423 S FEDERAL WAY
Project NameRoss Dress for Less
Customer Number 
ePlanReview 
Description
The Permitted Work Scope: Overhead Only
Beginning from an existing 6” underground supply spigot in the riser room, install a 4 manifold and wet riser to serve through out the interior of the store. The exterior will be severed from an auxiliary anti freeze system. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to permit BLD07-01188 and UG permit # FIR07-00897.04/29/08 Revised Work Scope: Overhead Only
The contractor added 38 additional pendant heads between the light soffits and the wall on all four sides of the bldg to meet coverage requirements. The modification was noted as Delta 2 & 2A, dated 04/18/08. This modification does not appear to adversely affect the operation of the system as designed.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/24/20086/24/20086/24/2008PPASS
DetailsForrest France
Correction notice items verified for completion, OH fire sprinkler permit finaled.
INSP-Final Inspection6/20/20086/23/20086/23/2008AFAIL
DetailsForrest France
Provide certification for the RPB, relocate the automatic ball drip for the fire dept. connection, provide missing "911" sign at the outside bell, provide pitot and playpipe for functional forward flow testing per review notes, need to attatch calc stickers, riser signage, state tag etc.
INSP-Sprinkler Rough-in/Hydro5/22/20085/23/20085/23/2008APART
DetailsForrest France
Hydrostatic testing for the new system piping branch lines and pendent heads passed.
INSP-Sprinkler Rough-in5/20/20085/21/20085/22/2008APART
DetailsForrest France
System modifications per plan resubmittals completed okay, will need a hydrostatic test for the new heads and piping, noted missing ball drip at the FDC, also discussed items needed for final including forward flow test, alarm interconnections, etc.
INSP-Conference3/14/20083/18/20083/18/2008ADONE
DetailsForrest France
On site visit regarding the requirement for extended coverage pendent sprinklers at the sales floor area to meet NFPA 13 2002 table 8.8.5.1.2(a) to avoid obstructions to discharge.
INSP-Sprinkler Rough-in3/3/20083/4/20083/4/2008PFAIL
DetailsForrest France
Overspaced head at the restroom area, EC heads adjacent to the south and west walls of the sales floor area do not meet table 8.8.5.1.2 per NFPA 13 for clearance to ceiling mounted obstructions.
INSP-Sprinkler Rough-in/Hydro1/28/20081/29/20081/29/2008PPART
DetailsForrest France
Hydrostatic tests for the overhead wet and antifreeze systems as well as the underground supply piping passed.
INSP-Final Inspection1/24/20081/25/20081/25/2008APART
DetailsForrest France
Overhead rough-in inspection only, noted one missing ret. strap, one missing hanger, two overspaced heads at the hard lid ceiling restroom areas, the antifreeze loop piping is not yet tied in to the riser, riser not complete at this time, see approved plan set for annotations, hydrostatic testing not ready due to start pressure well below 200psi., remainder of OH rough-in is acceptable.
INSP-Conference1/23/20081/24/20081/24/2008ADONE
DetailsForrest France
On site conference with regard to location of the FDC.