INSP-Final Inspection | 5/15/2008 | 5/20/2008 | 5/21/2008 | P | PASS |
Forrest France
|
|
|
All six items per letter dated march 28, 2008 to Ken Howell have been resolved.KR
|
INSP-Conference | 3/31/2008 | 4/2/2008 | 4/2/2008 | P | DONE |
Forrest France
|
|
|
conferences for the corrections that needed to be addresss per notes from Sam Rogers and Ken Roule.KR
|
INSP-Final Inspection | 3/5/2008 | 3/6/2008 | 3/7/2008 | P | FAIL |
Forrest France
|
|
|
Site inspection comments per K.Roule
Tested FA monitoring of VT and waterflow (by manual means). Both annunciated correctly at panel and offsite monitoring station. Visually observed location of dry sidewall sprinkler installed in exterior chimney. Work remaining on this permit:
1. Test the new fire alarm monitoring module which was installed on the existing cooking hood suppression system under this permit. (Requires the hood fire suppression system contractor to be present)
2. Test the waterflow alarm switch by flowing water from the test connection. (Requires the sprinkler contractor responsible for FIR04-00490 be present).
3. Provide fire alarm-initiated interlocks which shut off the hood exhaust fan and the gas fuel to the cooking appliances, as specified in the signed Fire Department Agreement dated 2/4/2004 and in F.Varley's letter dated 4 Feb 2002 letter (Item 2).
4. Correct the existing "trouble" condition on the fire alarm panel.
5. Provide an updated alarm map reflecting the current floor plan and all initiating device locations correlated with the annunciated fire alarm device addresses. (NFPA 72 4.4.6.1).
6. Replace the missing door latch on the FACP cabinet and update the outdated monitoring company and account information currently posted inside the cabinet.
|
INSP-Conference | 1/7/2008 | 1/8/2008 | 1/8/2008 | A | DONE |
Forrest France
|
|
|
On site conference to discuss hood suppression system interconnections to the building fire alarm system and programming for the new sprinkler WF and TS at the exhaust duct DSW.
|