Permit NumberFIR07-01018
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 9095 S FEDERAL WAY
Project Name 
Customer Number 
ePlanReview 
Description
02/04/08 Revised Scope of Work: Overhead Only
The overhead piping and calculations have been revised to include individual floor control valves as required. The original plans have been revised; the revision is noted as Rev. #1and dated 01/11/08.
Original Scope of Work: Overhead Only
The Underground scope of work was previously approved and the work was performed under separate permit # FIR07-00897. The overhead fire sprinkler scope of work includes installing a 4” wet riser and a grid system to serve through out the entire 26,000-ft/2 two story bldg. Any future racking plans in the warehouse area shall be submitted under a separate permit. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD07-02112 & UG permit FIR07-00897.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/7/200810/8/200810/8/2008APASS
DetailsForrest France
Items on C/N finished, forward flow testing passed, outside bell adjusted while on site, overhead fire sprinkler permit finaled.
INSP-Final Inspection10/2/200810/6/200810/6/2008ACANC
DetailsTroy Cobbley
Mike Bierman is the contact. Thanks. Phone #: ###-#### Internet Inspection Request from: Stan Beus
INSP-Sprinkler Rough-in7/11/20087/14/20087/14/2008APART
DetailsTroy Cobbley
The earthquake bracing as noted in the previous inspection has not been corrected and the upright heads on the second floor that were spaced too close together have not been corrected either. Leroy and I agreed they could be verified at the final inspection.
INSP-Sprinkler Rough-in/Hydro7/1/20087/2/20087/2/2008PFAIL
DetailsForrest France
OH rough-in inspection failed due to several items including 1st floor overspaced corner, elevator pit SW too high, noted added heads at entry vestibule, relocate EQ brace at office 103 if intended for the adjacent main longitudinal-see detail on plan set, warehouse area is missing proper temp. heads at the unit heater zones (13), noted two added heads and two deleted heads not required due to construction changes, one overspaced corner at the warehouse, 2nd floor office area missing two ssu heads, mixed temp. at one area, 4 heads exceed min. spacing, an additonal corner is overspaced. See locations marked in red on approved plan set for defficiencies. NOTE: Overhead hydrostatic test for both wet systems passed.
FIR-Aging Inspection5/6/20085/6/20085/6/2008 DEFR
DetailsForrest France
Need site inspection request