Permit NumberFIR07-01022
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 877 W MAIN ST
Project NameWELLS FARGO BUILDING
Customer Number 
ePlanReview 
Description
This fire alarm quick permit is to install heat detectors used for shunt trip purposes in the elevator hoistways, pits and mechanical rooms of the Wells Fargo Building. Heat detectors are required to be installed within 2' of each sprinkler head installed in the elevator equipment rooms and hoistways. No building permit is associated with this work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/27/20088/28/20088/28/2008PPASS
DetailsForrest France
Heat detector in frieght elevator control room was repaired and tested, per last inspection. KR
INSP-Final Inspection8/4/20088/6/20088/6/2008PFAIL
DetailsForrest France
Main elevator heat detectors in shaft, test completed.Heat detectors in main elevator control room, test completed. Heat detector in frieght elevator shaft, test complete. Heat detector in frieght elevator control room failed due to short in wiring need to re-test. Panel in trouble. KR
INSP-Conference3/18/20083/18/20083/18/2008PDONE
DetailsForrest France
Regarding after hours inspection scheduling.
INSP-Conference12/21/200712/24/200712/24/2007ADONE
DetailsForrest France
On site visit regarding heat and SD device locations at the elevator penthouse, hoistway and pit areas.