Permit Information
Permit NumberFIR07-01043
StatusFinaled
Name MOUNTAIN ALARM
Site Address 5246 W OVERLAND RD
Project NameHILLCREST SHOPPING CNTR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to modify an existing tenant space and provide audible visual notification throughout, HVAC shutdown and monitoring also installation of a manual pull station in the sprinkler riser room. Building permit BLD07-01556 is to combine two tenant spaces within the Hillcrest Shopping Center to create one 8,248 square foot branch library for the City of Boise. Selective demolition is also covered under this permit. Work is to include two restrooms accessible to the disabled, interior nonbearing walls, suspended ceilings, finishes, 'Solatube' skylights, and a new exterior concrete landing and stairway. In addition, one new opening will be created in an existing masonry wall. Steel headers and jambs will be provided. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/25/20083/26/20083/26/2008APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro3/19/20083/20/20083/20/2008PCANC
DetailsTroy Cobbley
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
INSP-Final Inspection3/20/20083/20/20083/20/2008PCANC
DetailsTroy Cobbley
Panel is not clear and has a supervisory for a low air do to a compressor that has malfunctioned. Brett Anderson of Mountain Alarm was notified that the issue will have to be resolved before fire alarm permit is finaled.
INSP-Final Inspection3/14/20083/19/20083/19/2008AFAIL
DetailsTroy Cobbley
Panel was not clear and had troubles for knox box monitoring and sprinkler system low air. Did not have an updated fire alarm map. No other testing perfomed. KR
INSP-Final Inspection3/10/20083/12/20083/12/2008AFAIL
DetailsForrest France
Descriptor for the new manual pull station is not accurate, need to provide an updated map at the panel reflecting correct floorplan and device locations, duct detectors could not be tested due to locked thermostat controls for the HVAC units, lock at the panel breaker installed while on site, one overspaced notification device repositioned while on site, 95cd ceiling mounted appliances not to exceed spacing guidelines, recommend lower decible settings at the restrooms due to sound pressure levels near 110 dBA at the minimum hearing distance, EOL voltage not tested at this time.