INSP-Final Inspection | 2/19/2008 | 2/19/2008 | 2/19/2008 | P | PASS |
Forrest France
|
|
|
Corrections are finished, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 2/13/2008 | 2/13/2008 | 2/13/2008 | P | PART |
Forrest France
|
|
|
Verified corrections noted at the previous inspection are compliant, overhead modifications are approved for cover at the drop ceilings, discussed need for a current annual inspection to be provided for the existing fire sprinkler system prior to building permit final.
|
INSP-Sprinkler Rough-in | 2/12/2008 | 2/12/2008 | 2/13/2008 | P | DEFR |
Forrest France
|
|
|
Duplicate inspection request.
|
INSP-Sprinkler Rough-in | 2/8/2008 | 2/8/2008 | 2/8/2008 | P | FAIL |
Troy Cobbley
|
|
|
Additional upright sprinkler protection is required in the combustible concealed space due to the new duct work obstructing the spray of the existing upright fire sprinklers. Also the existing riser needs to have a current inspection.
|